view in courier
SERVICE
LINE1 LINE2 120v 120v o o | | | | *-------(A)-------* | | | | * * \ DISCONNECT \ \ \ * * | | | | | | | | | | o o
LOAD
o o | | | | --- C --- C --- --- | | | | | | | *---------*---------* | | | | | | | | | | --- A --- B | | --- -/- | | | | | | | | | | (B) (C) | | | | | | | | | | --- --- | | - - | | | | | | | | | | o GENERATOR o
A is a mercury relay with a 240vac coil. B is a N.C. 120vac coil with 30amp contact. C is a dpst 120vac coil with 90amp contacts
When the disconnect is ON and the service is either ON or OFF,
- the generator is isolated from service feed
- the generator cannot backfeed into the grid
When the disconnect is OFF and the service is ON
- the generator isolates from the load
When the disconnect is OFF and the service is OFF
- the generator is connected to the load
The generator can't work or be damaged unless the disconnect is OFF.
I designed this circuit around some parts I had. The disconnect is in the breaker box.