Equipment is designed to operate +/- 10% of the nameplate rating. In the=


=20


case of taps like what happened here, the taps are supposed to be set by=

the=20


electrician to fall within the 10% range. With the taps set at 220v the =

CNC=20


machine was good to operate from 218v to 242v. As the power installer, =

it=20


was the electrician's responsibility to verify the voltage coming into =

the=20


building and adjust the taps on the machine accordingly. He was paid to=20
>correctly hook up power to the machine and failed to do so.
>

Don't you mean 198 V to 242 V?


Don't you mean 198 V to 242 V?

Why yes I did. Good catch!