Kinda off topic...House electrical issue?

I've noticed during moving one of the wall receptacles, that when the breaker for that circuit is shut off, I'm still showing 17-19vac on my meter. Not exactly sure as to why I'm still showing ac on a circuit that is supposed to be dead. I've checked a few others with the circuit breaker off and they too are showing 17-19 vac. The only thing I can figure is maybe some stray inductance or some sort of system ground problem. I've checked the breakers and everything seems to be fine. 200 amp main with breakers is less than a year old and I've always heard square-D is good stuff. Not sure....Any ideas?

Thanks, GW

Reply to
hk538
Loading thread data ...

I've noticed during moving one of the wall receptacles, that when the breaker for that circuit is shut off, I'm still showing 17-19vac on my meter. Not exactly sure as to why I'm still showing ac on a circuit that is supposed to be dead. I've checked a few others with the circuit breaker off and they too are showing 17-19 vac. The only thing I can figure is maybe some stray inductance or some sort of system ground problem. I've checked the breakers and everything seems to be fine. 200 amp main with breakers is less than a year old and I've always heard square-D is good stuff. Not sure....Any ideas?

Thanks, GW

Reply to
hk538

That's normal, if the wire is run parallel to another wire which is live you can get a significant voltage, though there should be next to zero current.

Square D is generally pretty good, you should measure the voltage at the terminals into the main breaker and turn on the A/C, it shouldn't drop more than a couple volts. If it does then you have a problem somewhere between the panel and the pole.

Reply to
James Sweet

What are you measuring with? If it is a high impedance voltmeter, the previous poster is completely correct. Connect a 1000 ohm resistor across the meter terminals. The voltage should be about zero. If it is not, then there is some serious coupling going on and you chould check further as there might be a safety issue.

H. R. (Bob) Hofmann

Reply to
hrhofmann

Hi Bob, The meter I'm using has a 10M ohm resistance. 1K rsistor in parallel with the meter leads, right?...Is this what's referred to as a shunt? Correct me if I'm wrong.

Thanks again, GW

Reply to
hk538

GW-

That is correct. You would be turning a 10M Ohm meter into a 1K Ohm meter.

The voltage you measure might be due to leakage current through the insulation resistance around the breaker. It might also be due to a small series capacitance between the input and output of the breaker, or a combination of leakage resistance and capacitance.

Either way, leakage impedance forms a voltage divider with the breaker input and your meter. Suppose the measured voltage is 10 Volts across a

10M Ohm meter. That means the leakage current is 10/10 microamps = 1.0 microamps. The leakage impedance would be (120-10)/1.0 Megohms =110 Megohms.

Leakage current of 1 microamp would cause a 1K Ohm resistor to develop about 1000 microvolts, or 0.001 volts. A digital meter might be able to read this on its most sensitive voltage scale.

Fred

Reply to
Fred McKenzie

Thanks for the information Fred. I really appreciate it. I'm hoping to have some time tomorrow after a Dr.'s appt to look into this a little further. Thanks again for the suggestions. Great help.

GW

Reply to
hk538

Thanks everyone:-)

GW

Reply to
hk538

Modern high impedance input DVMs are a bit of a pain for measuring household wiring. An old analogue meter with about 1000 ohms per volt is much more use.

--
*How come you never hear about gruntled employees? *

    Dave Plowman        dave@davenoise.co.uk           London SW
 Click to see the full signature
Reply to
Dave Plowman (News)

Leakage current in home wiring is often due to the presence of power factor correction capacitors in older flourescent light fixtures, and is quite normal

Arfa

Reply to
Arfa Daily

And with most SMPS. However, I was meaning testing with no load. UK house wiring is Twin and Earth - all enclosed within a sheath. This is a good system to keep external fields to a minimum, but allows a degree of capacitive coupling which with a high impedance volt meter gives very misleading results.

--
*Can atheists get insurance for acts of God? *

    Dave Plowman        dave@davenoise.co.uk           London SW
 Click to see the full signature
Reply to
Dave Plowman (News)

ElectronDepot website is not affiliated with any of the manufacturers or service providers discussed here. All logos and trade names are the property of their respective owners.