I'd guess that the outlet strip has MOVs line-to-ground that convert differential-mode currents into common-mode, and that trips the ground fault detector.
I'd guess that the outlet strip has MOVs line-to-ground that convert differential-mode currents into common-mode, and that trips the ground fault detector.
It trips when there is no current path to ground and no hazard. I define that as a false trip. I'd guess that the speed controller in the blender makes high frequency crud that fools the GFD.
If there is a break in the ring, the economical skinny wire will fry.
I thought redundancy/safety was a selling point of the ring. That requires fat wire.
We don't run a cable to each socket! One breaker feeds a bunch of loads. I don 't have a hundred circuit breakers.
in theory. Folk that have tested them are not impressed.
it doesn't, it's fine. It simply has less margin.
it is
too vague
still uses more cable & more breakers. Lots of houses here have 2 socket circuits, and it's no problem. New installs now get more than that.
- in most cases not required
I don't think I've ever seen a ring that drops 11%! If a circuit covered such a large area one would fit more than 1.
Re rings generally, I do notice that foreginers of all sorts seem to have a lot of confustion over rings, so do many brits. Despite their advantages the UK is afaik the only place that uses them.
To get a sizeable Vdrop increase you'd need 3 things.
Ultimately if you did all this, it would be way safer than a radial with the same fault
didn't know that
Have something to add? Share your thoughts — no account required.
Ask the community — no account required