Well, a 'spur' rated at 32A requires 6mm2 cable. You could calculate a voltage drop along that based on resistance data. There is AFAIK no limit on length aside from practical limitations ! I don't know how the incoming feed from the electric company to the breaker box might drop with load though.

Graham

In the US, it's no less than 5% drop from the source to the load at full load.. conductor must be rated to supply a min of 95%.

for example, 10 awg = 0.999/M or 3.28/kg ohms

of course, all conductors are based from copper, copper being 100% of the scale. All others are based from that. etc..

formatting link
"

I haven't looked it up properly but in the design of fixed installations you are not supposed to have more than a 4% voltage drop from the point of supply. So whilst 6mm cable will easily carry >32A, once you go over a certain length you would need to go up to 10mm to comply with the regs.

formatting link

Tim Phipps replace "invalid" with "uk" to reply by email

Thanks. Then from my calculations the maximum legal drop for any installation should be 13.6% from 240v - 207v and a bit, not including your own power distro.

Gareth.

Um, actually I think that's a bit innacurate as the 4% will be calculated for the power loss at 240v or even 254v? Close enough though.

Gareth.

Hah ! 230V -10%. That's what I test kit at when doing low voltage dropout tests.

Graham