RS485 grounding

Sep 19, 2008 23 Replies

There seems to be much debate on this with the searching I've done.



Let's say, simply you have a pretty long connection in a typical office environment between a transmitter and receiver, communicating one way via RS485 and a twisted pair.



I have always used a shield but only ground one end of it, usually wherever the "best" ground is....rcvr or xmtr.



However, I see also a great deal of discussion regarding grounding at both ends through 100 ohm resistors?


------------------------------------------------------------- A



------------------------------------------------------------- B



100 ohm............shield................100 ohm

What is that all about or should I care?


You shouldn't care if you can guarantee in some way that A and B will always remain within the common-mode range of the receivers at both ends.

But maybe there isn't a common ground.. or maybe there is but there is a small voltage between the two (with very low source impedance). Best regards, Spehro Pefhany

"it\'s the network..." "The Journey is the reward" speff@interlog.com Info for manufacturers: http://www.trexon.com Embedded software/hardware/analog Info for designers: http://www.speff.com

Ground both ends, hard, to the equipment chassis. Why would you want huge common-mode spikes on your data? Why bother with a shield if it's going to have nasty potentials on it relative to the signals?

John

You might also have some big currents flowing in the shield if the "ground" at each end is a different voltage.

Dirk http://www.transcendence.me.uk/ - Transcendence UK http://www.theconsensus.org/ - A UK political party http://www.onetribe.me.uk/wordpress/?cat=5 - Our podcasts on weird stuff
3 different answers -- actually I've been using just an unshielded twisted pair with no problems but I have had a couple of users with some transient problems.

I'm just using SN17576 chips on everything and opto-isolated to boot.

Perhaps they're using a shield.

You're saying DON'T use a shield?....it's just inviting problems?

My guess is the users are using cat5 twisted pair.....a worst case would probably be 300 feet of wire at most.

Only 1200 baud though.

org/- A UK political party

formatting link
Our= podcasts on weird stuff- Hide quoted text -

Which is why you sometimes "get by" by putting some resistance in one side of the ground connection. I see no reason to put 100 ohms at both end though.

George

The point of the resistors is to avoid nasty *currents* if the customer stupidly sets up a ground loop situation. There shouldn't be nasty potentials with 100R in there, certainly not relative to the CM range of the signals.

Best regards, Spehro Pefhany

"it\'s the network..." "The Journey is the reward" speff@interlog.com Info for manufacturers: http://www.trexon.com Embedded software/hardware/analog Info for designers: http://www.speff.com

So, in conclusion....

Use shielding when you can (or always?) and connect as I have diagrammed, a 100 ohm resistor from circuit ground to the shield on both ends.

What about protection on A and B as well?

Zener diodes to ground on each leg? (If so, what value woyld you use?)

I'm wondering as well if there is a plug in replacement for the SN75176B that has built in transient suppression?

Thanks very much.

The reasoning behind the resistor on each end is that cable runs sometimes get worn insulation and end up with the shield connected to earth ground somewhere in the middle of the run. The resistor on each end limits the current through the shield in such cases.

Guy Macon

Maybe 7V (bidirectional TVS not zener). And a series fuse of low current rating and reasonable interrupting capacity. The TVS adds some capacitance that might affect things at high data rates.

Lots claim to, especially the inherently fragile CMOS ones. Nothing on-chip compares remotely to a reasonably large discrete TVS. If you're lucky they'll survive a human body static discharge.

Worry about this a lot if your run goes on a roof, outdoors, or is fairly long (just the induced current from a nearby lightning strike can do some interesting things to solid-state electronics, and even passive compenents). Best regards, Spehro Pefhany

"it\'s the network..." "The Journey is the reward" speff@interlog.com Info for manufacturers: http://www.trexon.com Embedded software/hardware/analog Info for designers: http://www.speff.com

Thanks so much.

I'm starting with the TVS diodes and just twisted pair and doing my own "field" tests. I left out the diodes in my design and that may be the greater problem.

I'll play some "Ben Franklin" with a few setups.

Conventional wisdom is to ground only 1 end. Much more importantly (as you state) is to use twisted pair cable.

FWIW, someone could probably make a small fortune (cottage industry) making RS-485 protectors for DMX-512 applications. Much higher speed data than you're using.

Either shunts, clamps, opto-isolating. whatever!! For DMX stuff, this could all be housed in a male-female XLR-type "adapter". Put one at both ends (if opto) and totally isolate the copper! Or if clamp, one (at either end) might do the trick?

Anyway, we (our church) would be a customer. For sure. I'm suprised there is not more (and more affordable) protection devices out there for RS-485. Guess it's a matter of supply & demand?

Still, it seems once or twice a year the theatrical lighting controller at our Church gets absolutely hammered with lightning. It's installed correctly. The twisted pair is even in a metal conduit, and NO ground loops. I'm probably going to optically isolate the whole damn thing, but RS-485 was always billed as more "robust" than its single-ended counterparts....

-mpm

You don't say if the connecton is between two factilities. By factilities here, I mean two structures with separate earthing. If yes, then every RS-485 wires in each cable must be earthed where the cable enter than structure. Earthed means a connection to earth ground that does not conduct signals but connects everything else. Avanchle diodes are used but typically have too much capacitance. Other solutions include gas discharge tubes, Sidactors, or special low capacitance avanache diodes.

If the connection is internal, well, get Montandon and Rubenstein's Nov 1998 paper (IEEE Transactions on Electromagnetic Compatibility) to start learing (appreciate) what you must do.

Intall a good set of lighting rods -- you may only need one if you have a steeple -- with a proper grounding line.

References:

formatting link
formatting link
formatting link
formatting link

Guy Macon

Be sure to route the ground wire through the Baptismal pool ;-)

...Jim Thompson

| James E.Thompson, P.E. | mens | | Analog Innovations, Inc. | et | | Analog/Mixed-Signal ASIC\'s and Discrete Systems | manus | | Phoenix, Arizona 85048 Skype: Contacts Only | | | Voice:(480)460-2350 Fax: Available upon request | Brass Rat | | E-mail Icon at http://www.analog-innovations.com | 1962 | I love to cook with wine Sometimes I even put it in the food

I only ground at one end mainly due to over currents that can take place if for some reason large induced currents are near which is another reason you never lye the wire in the race way with high potential or high current rungs

Doing so will create some major problems of unpredictable cross talk of foreign signals down to damage on the RX/TX end points.

If you feel you must ground both ends, do the last end via a cap.

Also, in a heavy R.F. environment I like to keep the shield not connected to anything at the equipment and only ground it at the ground source. This helps remove any R.F. from traveling that could be generated from the equipment. Which is why I use a coax shielded ground with the shield not attached at the computer end but both the center and shield attached at the ground end. It grounds my PC via the center conductor, but also keeps the switching noise out of my radio equipment from the switching PS and other devices in my computer.

formatting link
"

It will be a lot more robust of you ground the shields on both ends. No RS-485 receiver likes a few kilovolts of common-mode voltage.

John

I once had to run a data link between two high rise building... around

200'. There was around 10VAC difference between the two "grounds" :-(

I "hard" grounded one end and used a resistor paralleled with a cap on the other end, and used transformer drive/receive on both ends.

...Jim Thompson

| James E.Thompson, P.E. | mens | | Analog Innovations, Inc. | et | | Analog/Mixed-Signal ASIC\'s and Discrete Systems | manus | | Phoenix, Arizona 85048 Skype: Contacts Only | | | Voice:(480)460-2350 Fax: Available upon request | Brass Rat | | E-mail Icon at http://www.analog-innovations.com | 1962 | I love to cook with wine Sometimes I even put it in the food

Ahh good, I hoped someone else put caps in parallel with the single resistor. Just keep the time constant well away from 60 Hz.

George

In general always connect the shield to the receiving end of something otherwise the shield will inject noise into cables from a noisy source. Keep in mind that resistors drop power and coupling the shields to ground through a resistive load with dissipate the noise as heat. Also all of this might not be necessary if you clean the tarnish off the ethernet male and female connections to ensure a low impedance connection. Also look for a star ground with lots of copper of metal for the sheild, hope this helps.

I'm EXTREMELY familiar with lightning abatement, but I appreciate the links. I don't know what the last event was at the Church. It does not have a steeple, but does have the usual high slope roof.

This last event took out our: Fire Alarm (required replacement external power supply for horn/strobe synchronization) The fire alarm itself and all the remote sensors, horns, etc... were fine. The PBX (a real no-name POS, but it works.). That just needed a reset. Security Panel (blew the power supply fuse - this is a separate system from fire alarm) One Newmark dual CD player. And finally, the Strand Model 300 Theatrical light controller. And I think that's it.

Because my license would not cover me, I chose NOT to attempt repairs to the Fire Alarm system, but it was pretty obvious what was wrong with it - once you wiped the soot away. It's a Kiddie system and I probably couldn't get parts anyway?

The PBX was not grounded, and apparently had never been since the day it was installed. (?) Also, no additional protection other than whatever's outside at the Telco.

The Strand is a longer story. It had been baked a couple times before. 1 Channel DMX512 was DOA long time ago. Before my time. Dimmer packs in the back room (48 of them at 2KW each) never seem to have a problem. The RS485 comm-link is another story. Twice that I know of, it blew out the LTC485 transceiver chips back at the dimmer paks. This IC sits in the middle of the board and litterally gets its top blown off (cracked, etc..) Very obvious repair - and luckily Strand did put these in 8-pin DIP sockets. (A clear indication of high failure rate item??) Fine traces on underside of board don't seem to be bothered... (which is a bit curious?)

Back on the other end (control room), the Strand 300 is basically a PC outfitted with some special software an a DMX512 (XLR-type) daughterboard to do the RS485 conversion. This is what went out this last time. (There are only 2 channels on this board, and as I mentioned previously, 1 was previously DOA.) The PC portion was fine, but no DMX output. The daughter board "looked" fine and everything you could visually ID metered OK. I suspect the problem was on the protection parts, but no schematic or parts availability so it had to go back to Strand this time. All fixed now, and at least we have BOTH channels restored.

The grounds look really good. Ditto for power. It's clear the comm-link is the weak link but I honestly don't have a good handle on how lightning is getting into this. It is twisted pair (looks to be 16 or 18 guage. Run is about 150 feet or so. In metal rigid conduit all the way - some of which is outdoors.

About the only thing I can think of is the cable is damaged mid-way in the conduit. But if I pull this out I'm just going to switch to fiber optic and be done with it.

I do have plans to check the grounding for the entire building... This is Florida so the soil is s^it. I use the term "soil" loosely. I should have said "sand". I suspect this last strike was close enough to put a fault current in the earth, given the extent of the damage. Oh, I forgot to mention it also char-broiled an 115-volt outlet that was running a window shaker air-conditioner. (AC is fine) Some of our neighbors also had reported damage.

The Church is old enough (and unfortunate enough?) to have crappy Zinsco breakers, but of course that's not the problem other than they cost an arm and a leg. But hey, God will provide....

By the way Guy, Martin Uman was one of my professors in college. Very sharp when it comes to lightning. Half of what I know about it I learned from him. He's got some really excellent texts out there if ever get your hands on one.

Your comments about the existance / condition of the lightning rods warrants further investigation. My "work" there is free (as in volunteering) so I don't normally dig too deep into what-ifs. (present situation excepted) I don't recall seeing rods, but there may be some, and if poorly grounded -- well then, that's not helping much!

-mpm