Re: Generator Hassles

Aug 09, 2010 4 Replies


The electrical service goes to the house. There are 3 underground 000


> cables that go to the barn from the house. The barn has a 60 amp breaker in
> the breaker box at the house. The 12,000 watt generator is in the barn. It
> has a 50 amp 240vac outlet, a 30 amp 240vac outlet and several others. I am
> hooking the 50 amp outlet to the house. I am using the same 3 underground
> 000 cables to send generator power to the house during a power outage.

sampe problem same solution.


A 90 amp contactor in the barn won't connect the generator to the house
> unless:
> 1. The electrical service to the house is off, and
> 2. The service disconnect switch at the house is off.
>
> When the generator is turned on, it tests the service disconnect at the
> house to assure the above two conditions are met. This is done by sending a
> 1 second electrical pulse to the house to see if it will actuate a coil. If
> the coil actuates, the 90 amp contactor latches open and prevents backfeed
> into the grid.

sounds unlikely to work.


If the service power turns on during that 1 second, the
> generator power and service power will clash and throw a 50 amp breaker to
> the generator.

if you're lucky.


--- news://freenews.netfront.net/ - complaints: snipped-for-privacy@netfront.net ---


Actually it'll probably blow his generator, and resolve the problem almost immediately... With luck, Jon will be fondleing it at the time.

r to

THAT IS CRUEL AND UNCALLED FOR YOU SOUND PERTURBED PETERD STOP FONDLING YOURSELF I WILL HELP YOU BEND OVER AND SPREAD WIDE

I AM PROTEUS

10 points to you..

that's now way it could go, another is the gernerator could phase-lock with the mains. and continue to run.

--- news://freenews.netfront.net/ - complaints: snipped-for-privacy@netfront.net ---

Join the Discussion

Have something to add? Share your thoughts — no account required.

Didn't find your answer?

Ask the community — no account required