disable cold junction compensation

Oct 16, 2006 4 Replies

I was wondering if anyone might know how to disable the cold junction reference on a Watlow 93 temperature controller.



I would like to use the controller to control the differential temperature in a heating system.



Thanks for any comments



Not specific to that particular controller, but if there's no firmware setting for it, you should probably be able to replace the sensor with a resistor.

Best regards, Spehro Pefhany

"it's the network..." "The Journey is the reward" speff@interlog.com Info for manufacturers: http://www.trexon.com Embedded software/hardware/analog Info for designers: http://www.speff.com

You want to measure temperature rise over something? What are the two sensors connected to?

YEs

I would like to measure and control the temperature increase of glycol as it flows through the ice field in an ice rink. I will control the temperature increase by adjusting the flow rate of the glycol.

Replac>

Use RTDs. These are usually wound copper and are very common sensors for temperature control in pipelines. Don't use this Watlow controller - go to Honeywell etc and look for a real differential controller.