I have two APC Back-UPS RS500 units which failed at charging the battery. It was a capacitor which failed on both of them and I have also found out that this failure is rather common for this UPS. Here is my description on how to repair them. If you have a similar problem that the UPS seems to work OK with a new and charged battery connected, but fails after a short time (days) with the 'replace battery' light on, then this could help you.



formatting link



Stig Vidar Hovland


Sir -

Did you notice any leakage around the capacitor? In other words, is this another possible "bad capacitor" fault?

formatting link
formatting link
formatting link
formatting link
formatting link
formatting link
formatting link
formatting link

w9gb

"w9gb" wrote in news:UIWdnZzbJ9Ou1Q7YnZ2dnUVZ snipped-for-privacy@comcast.com:

No leakage. I think the failure happens because of the combination of high temperature over a long time and low quality of the capacitor.

Stig Vidar Hovland