Think sigma-delta, or PWM, with the heater on/off being a one-bit DAC.

If you PWM the heater at a faster rate than the control loop, or if you run the output of the PID into a sigma-delta stage (that's either going as fast as, or faster than, the control loop), then the heater command will get low pass filtered in both the heating element and in the plant's thermal mass. This will make the heater & driver act much more like a continuous element than a relay element. At that point, a PID becomes fairly worthwhile.

--
www.wescottdesign.com
Reply to
Tim Wescott
Loading thread data ...

On a totally different line of thought than my previous response:

A traditional thermostat/anticipator acts, more or less, like a proportional-derivative controller with a relay output ("relay" is just control systems jargon for an on-off switch). There's usually hysteresis in the switch, but that's not uncommon with relay-output controllers, and it's the anticipator that -- more or less -- provides the derivative action.

(Note the "more or less" -- "sorta-kinda" might be better. At any rate, don't get wrapped around the axle if it's not exactly the same -- because it isn't.)

Such a system will still show some sensitivity of the long-term average controlled temperature to ambient conditions -- your plant (or house, whatever) will be a bit colder on average when ambient is colder, and warmer on average when ambient is warmer.

Putting a bit of integrator action into a controller like that will, perforce, guarantee that the average temperature of the plant is as close to correct as can be achieved with available sensors. It won't prevent the heat from cycling up and down, however -- that's a consequence of turning the heat on and off close to, or slower than, the thermal time constant of the plant.

Whether the benefit from integral action in the controller is worth the effort in such a circumstance is going to depend on the individual cases. I suspect that in general it won't, but I'm sure there are edge cases where it'll be all that's needed.

--

Tim Wescott 
Wescott Design Services 
http://www.wescottdesign.com
Reply to
Tim Wescott

You are describing things that are not part of the design I was describing. The control is to turn the heater on or off on each pass of the PID loop. The PID loop runs 10 times faster than the temperature measurement. I fail to see how this is any better than running the PID loop at the same rate as the temperature measurement. I also fail to see how the PID loop will improve on a simple set point with an anticipator.

--

Rick
Reply to
rickman

It is not clear to me that your assumptions are correct. For example, ignoring the issue of the anticipator, the idea that without an integral term in the control loop, the average temperature will be sensitive to the ambient isn't clear to me. Consider the controlled temperature as a function of time in two cases. In one case the heat leaking from the chamber is 1/10 the rate at which the heating element adds heat and in the other case heat leaks at 1/2 the rate of the heater. The control loop is a simple temperature set point with a fixed amount of plus and minus hysteresis. In the 1/10 rate case the heat will be on 1/10 of the time. The graph will be a saw tooth with the warming slope being 1/9th the width of the cooling slope. The average temperature will be the set point. The 1/2 cooling rate will give a sawtooth graph with equal heating and cooling periods... and again the average temperature will be the set point.

What periods of heating and cooling would you expect a PID controller could provide if it is not using PWM modulation of the heating, but rather the PID loop directly turns the heat on or off?

If heating a house, the furnace should not be cycled too often, so there is no opportunity to modulate the heat cycle over short periods. However, the system is question is an electric oven so such modulation would be possible, but only by adding another layer of complexity to the code which is not what is being discussed.

--

Rick
Reply to
rickman

Well, look at your critique about my level of detail, and then go look in a mirror.

Besides, you seemed to be talking about changing a design to make it better -- so I'm giving you ways to change a design to make it better.

Well, if you're just looking for justification in your thinking that a PID loop isn't going to help, then believe what you want. If that's your goal, then posting questions on USENET is probably a bad idea, because someone may tell you something that's contrary to your cherished notions.

So are you just looking for self-justification, or do you want to improve the performance of the system?

If you have a controller that's operating 10 times faster than the temperature measurement, and you want to improve the performance of the thing, then consider PWM-ing the output one way or another.

The anticipators that I know about introduce bias (they're basically heaters that warm the air inside a thermostat when the heat is on). So as the heat is on for a longer proportion of the time, the temperature seen by the regulating element (the bi-metallic switch, in this model) is, on average, higher than the temperature being regulated, which depresses the regulated temperature.

I'm sure that you're not dealing with an electro-mechanical thermostat, but if the control you propose is going to emulate it, you'll undoubtedly successfully emulate the problems.

I don't have the work to hand, but I've simulated a heating system with a typical relay-with-hysteresis thermostat: even without an anticipator, and in spite of the fact that a simple switch is often viewed as having "infinite" gain, simple on-off control does not regulate the long-term average temperature error to zero the way that a controller with an unbiased sensor and an integrator will. So in that regard, PID (or anything with a correctly applied integrator) is better.

--

Tim Wescott 
Wescott Design Services 
http://www.wescottdesign.com
Reply to
Tim Wescott

I'm not going to spend my free time simulating your system for you. That's what you're paid to do. So why don't you spend your free -- or paid -- time simulating your system for you?

I've done this stuff before, it's too long for me to remember the detailed answer, but I do remember that when you actually take the trouble to simulate the system, or calculate it's behavior mathematically, you find a dependency on average temperature with ambient.

--

Tim Wescott 
Wescott Design Services 
http://www.wescottdesign.com
Reply to
Tim Wescott

I get tired of discussions devolving into pissing matches. I'm trying to explore a particular point. Is a PID controller any better than a typical setpoint thermostat? No, I can't define every nuance of the question up front. But I'm not looking for ways to add complexity. I'm trying to understand the simple issues.

I'm not trying to tick you off, I'm sorry if my posts seem like that to you. You posts do seem like you are getting ticked off which is not my intent.

SED is a great place to learn little and get arguments at every turn. I don't have a system to improve the performance of. I am trying to understand if a simple PID controller is any better than a set point controller. I'm not looking for arguments. If you really can't discuss this without getting ticked off why don't we drop it?

I'm not trying to change anything, I'm trying to understand the issues in the existing concept.

Yes, the purpose of this is to "anticipate" the additional heating that will happen when the heat is turned off and the heat element cools down. The electromechanical thermostats do this with a heater, but a software approach can do it more effectively by estimating the cooling rate of the heating chamber (simple time measurement).

I think that is an oversimplification of the situation. The mechanical thermostat typically has a large hysteresis which is very overdone. A software set point controller can use any size hysteresis appropriate.

I'm not sure how important a long term average value is in most cases. Perhaps if you were controlling a crystal oven that might be an important point. In this case the oven just needs to be regulated to a narrow hysteresis range. I'm trying to understand if a simple PID controller adds anything to the picture other than complication. I'm not trying to make it any more complicated. The data shown for the existing PID controller (which is likely not tuned perfectly) is clearly not as good as could be achieved with a set point controller. It shows lots of rather random excursions. On the other hand, all of this is overkill for the application and far superior to the mechanical controller it has replaced.

--

Rick
Reply to
rickman

I'm not asking you to simulate anything. I just described a system simple enough to be simulated in your head and gave you the result. It may be somewhat unrealistic given the vagaries of real world situations, but it is clear enough to show a set point controller maintains an average temperature controlled by the set point when the cooling losses are constant, at least to a first order approximation.

--

Rick
Reply to
rickman

Well, there you go. You're smarter than the resident control expert.

Have fun!

--

Tim Wescott 
Wescott Design Services 
http://www.wescottdesign.com
Reply to
Tim Wescott

Rick may not want to be "prickly", but he often comes across that way. I'll take him at his word though. No insult intended Rick, but smart people sometimes are less adept at the social graces.

Besides driving the error signal to zero, doesn't a PI controller also have a faster response, compared to just P? Instead of a flat gain, you get more gain at lower frequencies. (That might not be right.. I'm far from a control expert :^)

George H.

Reply to
George Herold

Certainly there is no intent to tick people off. I guess it just comes naturally... ?? I consider it to be a shortcoming of the medium. I write with a deadpan emotional intent, most of the time, but I guess it must be read as though I am trying to offend.

I really don't know what Tim is ticked off about. I give a *very* simple example that can be considered entirely in your mind and describe the results. Tim seems to think it requires simulation and gets mad about it when I point out how simple it is. Or maybe I'm not understanding what he is upset about. Don't know.

Ok, but your model assumes there is some variability to the control I think. If the control consists of deciding on each cycle of the PID loop whether to turn the heater on or off, how does a PID controller improve response? If the desire is to turn the heater on at a smaller deviation from the set point, the hysteresis can be set closer to the set point, no? To be honest, if you don't care how often the heat is turned on, why would you even need hysteresis? Just turn on the heat when the temperature is below the set point and off again when the set point is reached. Then the only issue is the overshoot from the thermal mass of the heating element. An anticipator can help with that.

The other point was that running the PID loop faster than the temperature is updated seems pointless. The person who has designed this approach creates a process for each part of the algorithm, one for measuring the temperature, one for running the PID and others. I'm not clear at all why he thinks the PID is usefully run faster than the temperature is updated. I can't get anything out of him other than because "it's fun". I'm just trying to understand how a PID controller can work better than the set point controller when there is no proportional control over the heat, just on and off.

The only thing I can think is that the PID, when properly designed, will inherently consider the thermal mass of the heating element while with the set point controller it has to be accounted for by an anticipator. Even so, I don't see the two as much similar, is that wrong?

BTW, who is "the resident control expert"?

--

Rick
Reply to
rickman

formatting link

-Lasse

Reply to
Lasse Langwadt Christensen

Ha!

Reply to
Cydrome Leader

I have a copy. It's a pretty good book, though I'm really not a control guy myself, so it may be better than that.

Cheers

Phil Hobbs

--
Dr Philip C D Hobbs 
Principal Consultant 
ElectroOptical Innovations LLC 
Optics, Electro-optics, Photonics, Analog Electronics 

160 North State Road #203 
Briarcliff Manor NY 10510 

hobbs at electrooptical dot net 
http://electrooptical.net
Reply to
Phil Hobbs

Only for certain plants, but yes, often a PI controller can drive things close to target faster than just a proportional can. And when it happens, it's because of more gain at lower frequencies.

--

Tim Wescott 
Wescott Design Services 
http://www.wescottdesign.com
Reply to
Tim Wescott

dp/0750678399

Pretty good for people who aren't control experts is what I was aiming at (hence the "applied"). I wouldn't recommend it to a control expert unless they wanted a book to hand out to people, or possibly if it's someone used to doing things in analog and they wanted more familiarity with doing things in digital-land.

--

Tim Wescott 
Wescott Design Services 
http://www.wescottdesign.com
Reply to
Tim Wescott

Look I work with temp controllers alot and I can most likely fill in some of your gaps for you.

First of all, lets get to the issues at hand you seem to be stuck on.

COntrollers for one have a tuning mode, you set the temp and initiate it. It'll cycle for a while and there are some parameters it'll set.

P = Gain/BW depending on the maker of the controller. I = Integrated readings of the PV (process value)

D = rate of change which can be used to dampen the PID output. +/- Btw, some D's only work once it starts to get near setpoint, others will work across the whole stretch.

Also on top of all this....

You have soak time that can be programmed for many controllers in various ways.

Output power:

This helps in the case of large mass. Output duration can be set for a max/min effect, reguardless if it reaches desired set point or not.

In water cooling systems, you can adjust the output power so to not over cool per cycle. All this does is turn on the cooling for short pulses when needed. Heating is also done the same way. For systems that have large mass it can over shoot and take too long to correct. The output of the controller simply pulses a short ON pulse and the duration between is done via the PID terms.

In otherwords, if you remove the PID out of the picture and use only power output settings, you can simply set the max ON time for heat or cooling. Some systems use a Duty cycle parameter instead of a MAx on time. Others use a Max On/MaxOff same as duty cycle.

If the controller has a 0..10/4 to 20mA output, it does not pulse, it simple does not go to full output at all when adjusting power bands.

On top of all this, Many controllers have a percentage of direct and PID control, meaning the PID only effects the output a certain percentage over the direct output.

A non PID controller is basically something that just has a Power band set and when it reaches setpoint it just turns off. When the temp drops a little, it turns on, when it gets a little too hot, it turns on the cooling, using the cooling's power band settings and there is a dead band setting.

I work with various controllers, many of them PLC's that have built in PID loops and found that most of the time they work fine however, there are times where I've had to intercept on the PID output to add a little control of my own. Things like a power band for example.

I have also found in some cases, there was just no way to to use a basic PID due to changing events out side the norm.

have a good day

Jamie

Reply to
M Philbrook

That's been answered! Just read!

If you're going to refuse to use well-known useful techniques like PWM-ing an ON/OFF output, or using a sigma-delta modulator, then yes, an old traditional bang-bang controller with an anticipator may work best.

But why refuse to use well-known useful techniques?

If it's properly tuned it may lead to better precision by turning the heater on or off part-way between temperature measurements. That doesn't mean that it's a good decision, that's just a (very slight) advantage that it may have.

OK. So your real concern is that you've got some out of control designer, presumably a software guy, who's so severely unprofessional that he's letting himself be motivated by what's "fun" instead of what's best for the project. Meaning that he could do something just as "fun" with bang-bang control, to an equal level of dismay on your part. So the basic problem you're trying to address is only incidental to the PID controller.

(BTW: "because it's fun" is very occasionally an allowable excuse for doing something in my book, but generally only if there's plenty of slack in that part of the project, the guy's attention isn't needed elsewhere, AND if the guy has a track record of giving up on the "fun" stuff if it isn't panning out. If someone is sticking to something substandard "because it's fun" at risk to the project, then they need to be encouraged, possibly with a pink slip, to go find a more "fun" place to work.)

Well, I already told you that, several times. Possibly because I took your questions at face value.

They're not all that similar, and there's no reason that a bang-bang controller might not be inherently better in certain circumstances -- but whether a PID is better than bang-bang or visa-versa depends on the plant and what you're trying to do with it. There's no one right answer.

The above assumes that each controller is designed by someone who cares. Certainly, a bang-bang controller designed by someone focused on getting decent performance has a very good chance of outperforming anything designed by a guy who doesn't give a shit about doing a good job if there's "fun" to be had.

Certainly, if a bang-bang controller is so far better than adequate that no one could want anything better, and if that bang-bang controller isn't adorned with an anticipator that's more ornate than the PID controller that might be used instead, then it's probably the way to go -- no matter how "cool" the PID controller may be.

There are cases, in fact, where bang-bang control may well be superior. If you get a PID controller all tuned up to within a gnat's eyelash of perfect for an empty oven, it may have a horrid, even an unstable, response to an oven with a big thermal mass in it (even if -- or possibly especially if -- it has nice PWM'd output). Ditto if you tune it up for the big thermal mass and then try to run it with an empty oven.

It's been known since the 1950's that bang-bang control can be a much better alternative to either robustly tuned linear control or to on-line adaptive control -- in fact, the signal motivation for adaptive control theory (aside from the pretty math) since the 1960's was that bang-bang control works scares the bejabbers out of a human pilot, however well it works in an unmanned missile. This leaves the control system designer contemplating robust or adaptive control of some sort.

Has this question been answered to your satisfaction?

--

Tim Wescott 
Wescott Design Services 
http://www.wescottdesign.com
Reply to
Tim Wescott

All valid observations if he's using a prepackaged temperature controller. But from the sounds of it they're building a temperature controller into some embedded software.

--

Tim Wescott 
Wescott Design Services 
http://www.wescottdesign.com
Reply to
Tim Wescott

Rick, I stopped reading, I don't really understand alot of whatever you are trying to say. You can simulate control loops in spice, or build 'em and measure.. then post circuits.