Dual-purpose 3-phase motor?

Aug 02, 2007 2 Replies

In my business I come across old German equipment with 3-phase induction motors that are connected in Y-configuration to start and within a few seconds switched to delta for running. This is done, I'm told, to lessen the inrush current at switch-on.



Typically the motors have 3 independently-wound windings with 6 connections, both ends of each winding are brought out to the terminal block.



I'd like to understand a little more about why this works. Is it as simple as the fact that between 2 supply phase connections in the Y configuration there are 2 windings and in delta there's only 1? (The Y configuration's common point is not connected to ground or neutral.)



Thanks,


Al, the usual

You have it, except that there is a phase angle between the windings, so they do not share the total voltage as if they were two independent inductors. Instead of the volts per turn dropping by half, it drops by a factor of 1/square root of 3.

formatting link

Thanks, John. Much clearer now. Good reference.

Al, the usual

Join the Discussion

Have something to add? Share your thoughts — no account required.

Didn't find your answer?

Ask the community — no account required