220V Service line

Feb 28, 2026 Last reply: 4 months ago 1 Replies

Setting up a new shop, but will need a 220 line for servicing some high power equipment.



This transformer sits on the floor near the breaker panels:



General Electric 9T23B3872

formatting link
Specs say it steps down 480 to 120 and 208.



Is 208 gonna work for 220? Never heard that voltage mentioned in my travels.



The 120V wall outlets read about 123V on the DMM, sort of high than where I was previously.


Hopefully you have a real electrician coming to do the installation--480V mains power is no joke whatsoever.

208 is the nominal voltage across two phases of a three-phase feed. |240*sin(120 degrees)| = 207.85.

I once had an actual electrician mistakenly connect 208 to a 240V single-phase load (a brand-new, fancy lamp-pumped Nd:YAG laser). This effectively browned out the internal switching converter, resulting in overcurrent large enough to cause the (underrated) fuseholder to catch fire.

Exciting times in the lab. :(

Cheers

Phil Hobbs

Join the Discussion

Have something to add? Share your thoughts — no account required.

Didn't find your answer?

Ask the community — no account required