Hitno mi je potreban PC/PPI kabel za Siemensov S7-200 PLC. Bilo da mi posudi (uz naknadu naravno) dok ne narucim novi (ca. 10 dana) ili da mi proda svoj. Sve moze na mail : snipped-for-privacy@hi.t-com.hr



Hvala !


Probaj ovo, mozda ce biti brze nego naci zamjenski kabel:

formatting link

The PPI cable is a simple data-driven RS232-RS485 converter, powered by the PLC.

The pin configuration for the RS232 side is:

  • 2 - Received Data (PC listens) * 3 - Transmitted Data (PC Sends) * 5 - Signal Common

At the RS485 side you have to find:

  • 1 - Shield (also PLC logic common) * 2 - GND (PLC logic common) * 3 - Signal B * 7 - +24V power from the PLC * 8 - Signal A

Baudrates are selectable between 600, 1200, 2400, 9600, 19200 and 38400.

Kind regards, __________________ Jean Pierre Vandecandelaere