** The amount of saturation shown is entirely normal for the class of transformer - it makes the unit smaller and have better regulation than otherwise. Your scope trace for Imag shows no sign of there being a resistive ( in phase) component - so no shorted turns.
I have a very similar ( Dagnall) tranny here and ran an off load test to see how much the primary temp rose.
Primary R went from 757 to 815 ohms, after two hours on the bench.
Equates to an internal temp rise of just 19 degrees.
awkward that it is encapsulated. Sounds like the laminations are not properly assembled. I've had transformers with a gap of 2mm between the E and I 's. Result - much higher Imag and overheating. Solution was to return to supplier.
This seems quite high for no-load copper losses. Have you measured the magnetizing current for the similar Dagnall transformer you have?
I have a 12 VA transformer that draws 32.2 mA unloaded from 120 VAC, and the primary resistance is 50 ohms, for a no-load copper loss of .0518 watts. The total no-load loss, copper+core, measured with an accurate low power factor wattmeter is .48 watts.
I checked a couple more small transformers and the no-load copper losses are more like 1/2% to 1% of the full load rating, rather than 10% as the OP is getting.
Bear in mind that that Imag is largely reactive. It does NOT represent actual dissipation as VI or are you not familiar with the difference between real and apparent power ?
I make 57mA into 400 ohms, 1.3W of copper losses. No big deal.
In this particular case we needed 50 transformers.
Clairtronics were probably the biggest supplier of this type of transformer in the UK as they had distribution tied up with most of the catalogue companies. The demise of Clairtronics disrputed the supply chain as Farnell etc were all looking for an alternative source.
In this situation it was a matter of getting transformers from where we could at a sensible price.
Given that we had on going field failures with the Clairtronics transformer from a batch of 900 purchased 3 years ago I am being cautious in making sure I understand the difference in performance.
Phil poked me to cross check the temperature rise which has shown my infrared thermometer is reading 20C high. That is my fault I should have realised if I didn't burn myself when I touched the transformer it could not have been 95C.
And my fault for not having the thermometer regularly calibrated. It is now on the list with the rest of the kit.
The German manufacturer has confirmed the Imag currents etc are normal and not a problem.
I spoke to several UK transformer manufacturers yesterday and they all now import this type of transformer despite web sites saying made in the UK. It is a low cost commodity product and everyone is cutting corners to keep the price competitive. I just have to accept they will run hotter than I am used to.
But the fact that it's getting hot means there's quite a bit of resistive power dissipated as heat.
I did some work for a transformer co many years ago (Belclere) and their stuff was conservatively designed and got gently warm with no load. I guess they are driving the cores much harder these days, but would still reject any transformers that get significantly above ambient with no load. The quoted 75 C is way over the top. Just cheap 'n tacky design imo.
That's quite apart from any green issues w/regard to power efficiency...
Raveninghorde mentioned more than 400 ohms hot, IIRC 466 ohms warmed up with no load. That's 1.5 watts copper loss in the primary, plus core losses. Total heat dissipation with no load is probably almost 2 watts, which is enough to warm up a 10 VA transformer quite a bit.
A 10 VA transformer dissipating almost 2 watts with no load, maybe
2.5-plus watts with full load... Drawing 13 VA with no load... It sounds to me that the manufacturer really cut corners. I am guessing that the core material is only a step or two better than recycled truck bodies, the laminations are a bit on the thick side and the primary turns count is on the low side.
I am also guessing that the transformers were designed for 230V, but I have heard that many parts of England have 240 (True?). If this is true, then cores that already saturate somewhat will do so even worse.
Round here, 240 volts on the dot most of the time, perhaps 238/239 at cooking time. Transformers in the old days would take a few percent either way, though I do remember old valve equipment that had tap settings in 5 or 10 volt steps. Probably more to do with internal calibration than anything else though.
Everything gets cheaper and tackier and quality kit can't compete where everything is rated on 'how much does it cost', rather than 'what does the product really need to be a sound engineering design'...
The 57mA off-load Imag figure is of academic interest only.
Cos when on load, it drops by a factor of nearly 4 times, reducing the related copper loss by a factor of 14 and so becomes insignificant.
If the tranny is operated with 60 Hz power, Imag drops by a factor of 3 time off-load and 6 times when loaded - making the related primary copper loss trivial in both cases.
ElectronDepot website is not affiliated with any of the manufacturers or service providers discussed here.
All logos and trade names are the property of their respective owners.