Two months ago I was searching connectors for a power supply from Emerson R48-3200 (48 volts 3200 watts) Someone from this group indicated me JONHON in china, it was exactly this manufacturer! Thank you for this nice input, I've ordered few of these connectors and powered up this power supply today. Now I need to find the operational manual and if it exists the service manual. At least the op manual to be able to configure this ps. I believe there is a digital bus to be able to configure the parameters and to ger the status and alarms. I've contacted Emerson but no answer from them. Could someone help me again?



Many thanks in advance. All the bests. pf


On Mon, 07 Mar 2011 22:41:22 +0100, "Pierre-François (f5bqp_pfm)" put finger to keyboard and composed:

Google turns up several hits for Emerson products that incorporate the R48-3200 (p/n 1R483200) rectifier:

formatting link

This catalogue has several references to the rectifier and compatible controllers (eg M500D, M501D, M800D):

formatting link

FWIW, the "RELATED DOCUMENTATION" page in the following document lists several document numbers:

SAG588250400 / SAG588250300 System Application Guide:

formatting link

Schematic Diagram: SD588250400/SD588250300 Wiring Diagram: T588250400/T588250300 System Instructions: UM588250400/588250300 Rectifier Instructions: UM1R483500e ACU+ Controller Instructions: UM1M820B SCU+ Controller Instructions: UM1M521B

- Franc Zabkar

Please remove one 'i' from my address when replying by email.

Le 08/03/2011 04:00, Franc Zabkar a écrit :

formatting link

formatting link

Hi Franc, & the Gang,

Thank you for your reply, yes I've all these I found on yahoo search, but no more. Someone from Emerson Network Power told me that these power supply products are managed by Emerson Systems Group, he gave me a generix email address but they aren't responding. Emerson Network Power told me they cannot help more, they don't have these informations.

All the bests pf

formatting link
and
formatting link
have both been inactive since may 2009.

Current software support:

formatting link

RL

Part of Netsure A50B50 product,

formatting link
or Arcturus
formatting link

Communication with SCU is by CAN bus.

In the good old days, you just plugged the damn thing in.

RL

Le 08/03/2011 15:29, legg a écrit :

Hi RL,

Yes there is a SCU to control this ps, I would like to find the manual to build a home made SCU. I've just tested the ps connected to a dynamic load, I could run it at

45.7 Amps / 54 Volts during half an hour. My dynamic load is limited above 2kw, I couldn't test it up to 3.2kw... ;-( The ps is almost fresh, and in pulse mode at 2.4kw the output remain stable like a rock! Now my only problem is I cannot change the output voltage down to 48V and visualize the alarms.

All the bests pf

It's a rectifier for 48V: default would be full current into the battery system, to allow charging to achieve a 'float' voltage of roughly 54V. It's strange, though, that this default doesn't time-out on a communications fault, or some other fail-safe. Perhaps that is unnecessary.

Most 48V system hardware will like 54V, this being within their normal operating compliance range. Some even allow operation to a 60V system float level (an economy of scale).

RL