In fact, large numbers of switching power supplies on a three phase system require a larger neutral than the same system with a purely resistive load. This is due to all the harmonics generated by the power supplies that have no power factor correction. A number of fires in offices and factories occurred when large numbers of switching supplies were installed, starting about 20 to 25 years ago.
I had a neutral fire in the breaker box for a CATV headend in 1985 due to all the harmonics caused by the newer equipment we were installing.