Dielectrically Isolated?

Hi

I'm in the market for a stepdown transformer, and in my research i am finding the following....

The specs say: This is not dielectrically isolated. What does that mean, and how do I know if I need it to be isolated?.

Cheers

Reply to
Spankalogical Protocol
Loading thread data ...

"Spankalogical Protocol"

** That means the unit is not a normal transformer with separate primary and secondary but an "auto-transformer" with a single winding having a tap ( a connection some way along it) at the desired voltage.

If you have some item of gear intended for the US or Japanese markets so built for a 115 volt AC supply - then you need to examine this item and remove any caps connected from AC to ground or chassis.

When you care to " get real" and post just what the stepdown unit is AND your intended use is it MAY become possible to give more advice.

........... Phil

Reply to
Phil Allison

Not sure I realy understand this bit Phil, can you tell me why? Inrush current? DC offset if load is negligently put between tap & active instead of tap & neutral?

Thanks, Alf

Reply to
Unbeliever

"Unbeliever" "Phil Allison"

** When using a 240/115 auto-transformer it must be assumed that either or both supply leads to the 115 volt appliance will be at 240 volts AC relative to ground. This will happen if the active and neutral wires are swapped at the AC supply outlet ( including any re-wired plugs, extension leads and multi-outlets), the lead going to the step down or by simply a having a missing neutral anywhere in that path ( eg an AC switch is in the neutral or a ill fitting plug and socket).

Typically, the caps fitted from AC to chassis ground in 115 volt appliances are not able to cope with 240 AC mains supply and will develop a dead short at some time. Also, some old US appliances simply have no ground yet still have a "ground cap" - these become quite lethal if used with an auto-transformer.

BTW : There is no electrical standard covering auto-transformers of this sort (ie those fitted with AC lead and US style outlets) so no way they can be type approved. It is illegal for an electrician to install such a transformer for general use - it is a prohibited item under AS 3000.

.......... Phil