Circuit breakers seem to do the same thing. I have a situation where I have to draw more than the 15 Amp circuit rating. If I do this for 15 minutes or so, the breaker pops. So I limit the overload to 5 minutes and the breaker stays on.
This is an undesirable and temporary situation. The parts needed to fix the problem arrived yesterday. All I need is the time to put it together.
But I think you may be able to overload a circuit for a limited time without blowing the breaker. Don't overdo it. You might burn the house down!
Thermal breakers do that on purpose. You can get thermal-magnetic breakers as well, which are much faster but iirc have the annoying habit of tripping when some motor starts up. (My joint has all thermal breakers.)
Cheers
Phil Hobbs
--
Dr Philip C D Hobbs
Principal Consultant
ElectroOptical Innovations LLC / Hobbs ElectroOptics
Optics, Electro-optics, Photonics, Analog Electronics
Briarcliff Manor NY 10510
http://electrooptical.net
http://hobbs-eo.com
** Thermal-Magnetic breakers (aka MCBs) are standard items on distribution boards. Intended to protect building wiring much the same way as old fashioned fuse wire did, with the distinct advantage of be easily resettable.
The internal design is non-trivial but how they behave is simple enough.
Used at or below the nominal current rating, the breaker should never trip.
Exceed the nominal amps figure and wait long enough and it will, a high ambient temp will make waiting time less.
A larger overload (5 times or more) causes the breaker to trip almost instantly by virtue of a magnetically operated latching switch in series with the bi-metal one.
10 or 20 times overload reduces the delay time to a few milliseconds or a small fraction of one AC cycle.
Like HRC fuses, MCBs are rated to break very large currents, thousands of amps if need be.
BTW:
MCBs work just as well in 12V DC circuits as they do with 120/240V AC ones.
Saves carrying around and using up lots of wire fuses in some situations.