Actually they did change the rule concerning derating a few years back, due to what you mention. Before, pretty much only that portion of the total building load comprising the lighting could NOT be derated. (and the first 200 amps of non-lighting load)**. The neutral was generally smaller than hots. Now, it's going in the other direction.

Lighting Ballasts were a big offender, with electronic ones even worse.

All the newfangled stuff seems to cause harmonics, which are additive in the neural conductor. That could make the Neutral current greater than the line current.

You inspired to me to find out how bad this stuff is. The following PDF file has some rather interesting tables.

formatting link

It appears some electronic ballasts can have UP TO a thirty third degree Harmonic. Wow. That's more than Freemasonry has.

**(Canadian rules.)

mike

Reply to
m II

Rectifiers generate harmonics (no surprise).

The "triplen" harmonics - 3rd, 6th, 9th, ... - add instead of canceling on a 3-phase wye neutral.

-- bud--

Reply to
bud--