sending 12V signal from a Barcode Scanner to a PLC?

Anyone has any advise on how to send 12V signal from a Barcode Scanner to a PLC?

Thanks

Reply to
LongBow
Loading thread data ...

Scanner to a PLC?

Hi, LongBow. Choose a barcode scanner with RS-232 output, and a PLC (programmable Logic Controller, an industrial computer with built-in I/O generally used to run machines) with RS-232.

Most of your difficulty will be in programming the PLC to deal with the character string and the PLC serial buffers. Sorry, no recommendations on which barcode scanner to buy. I decided to use a PC in place of a PLC for that machine the time I tried it. The tradeoffs led me to decide the additional hardware hassles of a PC would be compensated by the much easier software route (including drivers from the barcode manufacturer). Try to pick the easiest way to reliably solve the machine.

Also, if you're doing it this way, try not to get a free-running barcode scanner. The PLC serial buffer can be impossible to deal with when it overruns, and resetting things can take forever. You don't want this hassle, and you never get the flexibility in a PLC you have with a PC serial port. Get one that sends data on trigger (either a button on the scanner, or on a signal from the PLC)as an option. This is another issue where having a PC instead of a PLC solves a lot of problems, especially if you've ever programmed serial comm.

Another thing you might want to try is to call the apps engineers at the manufacturer of the PLC you like. They're usually very helpful, and frequently will provide sample software for their preferred barcode scanner.

Questions of this type usually receive a better reception on sci.engr.control. Try posting there for a lot more advice.

Good luck on your project Chris

Reply to
Chris

PLC?

not sure in what form you need the signal?

if you get a RS-232 type, the output should be around

12 volts. of course you need to decode RS-232 protocol. some PLC's do have a RS-232 input that you can use in the latter logic.

if all your looking for is to create a trigger from the output of a scanner to signal the PLC that it's scanning ? i guess you could use a simple op-amp to bump the voltage up. i don't have a Ascii utility to draw it here for you but i will explain.

using a TL082 op-amp or similar with a + & - 12 volt supply

the + input is the input to use from a on condition signal from the scanner ( even if its pulsed), the - input will have a Resister to ground(common)R1, also the - input will have a resistor to the output of the Op-amp R2. now, you need to calculate the 2 resistors to get your proper gain that you need. Gain = (R1 + R2) / R1

or the reverse to come up with some Resistors. lets assume the logic from the scanner is 5 Volts. Gain would need to be 12/5 = 2.4

now to come up with total T network. in this case i will use 10K to start with.( because i like 10k :)); R1 = 10,000/2.4 = 4166 ohms. R2 = 10,000-4166 = 5834 ohms.

of course those are strange size resistors. you would have to round them to the nearest that you can find. the output of the op-amp can signal a PLC input. your latter logic would have to account for pulses if that is what your monitoring?. etc.. just an assumption on my part! :))

Reply to